| E166099 | ||
| Cat. No. |
Wire Range |
Wire Type |
FW |
TQ Lb In. |
V |
A |
UG |
CA |
|---|---|---|---|---|---|---|---|---|
| 22-14 | CU | 2 | 2.8 | 250 | 16 | B,D | 2(95),4 | |
| 22-14 | CU | 2 | 2.8 | 250 | 16 | B,D | 2(95),4 | |
| 22-14 | CU | 1 | 2.8 | 300 | 16 | B,D | 2(95),a | |
| 22-14 SOL | CU | 1 | 2.8 | 300 | 16 | B,D | 2(95),a,b | |
| 22-14 STR | CU | 1 | 2.8 | 300 | 8 | B, D | 2 (95), a, b | |
| 16-22 SOL | CU | 1 | — | 300 | 8 | B,D | 2(95),a,c | |
| 18-22 STR | CU | 1 | — | 300 | 8 | B,D | 2(95),a,c | |
| 12-22 | CU | 2 | 6.2 | 150 | 9 | C | 2(105), 4,d | |
| 12-22 | CU | 2 | 6.2 | 300 | 9 | D | 2(105), 4,d | |
| 12-24 STR | CU | 2 | 3.1 | 300 | 11 | B, D | 2(65), 4, e | |
| 12- SOL | CU | 2 | 3.1 | 300 | 13 | B, D | 2(65), 4, e | |
| 22-18, STR | CU | 2 | 3.0 | 300 | 10 | B,C,D | 2(105,4 | |
| 22-14, STR | CU | 2 | 4.4 | 300 | 10 | B,D | 2(105,4 | |
| 22-12, SOL/STR | CU | 2 | 4.4 | 300 | 20 | B,D | 2(105,4 |
(a) The insulating material is used at a thickness below its Recognized minimum thickness on the ends of these terminal blocks. Spacing between the ends of the terminal blocks and live parts and dead metal parts should be maintained in the end product.
(b) The static heating test on Model 320 was conducted in conjunction with mating connector Model 321. The acceptability of the combination shall be judged in the end product.
(c) A pull out test per paragraph 26.2 or UL 1059 was conducted on the spring force terminals. The minimum force required to spearate the conductor from the terminal was 10 lbs for 16 AWG SOL and 18 AWG STR, 18 lbs for 22 AWG SOL, and 4 lbs for 22 AWG STR.
(d) The suitability of the connections to the push-in terminals shall be determined in the end product.
(e) The static heating test on Model 326 was conducted in conjunction with mating connector Model 327. The acceptability of the combination shall be judged in the end product.
(f) = 520 followed by 2-12 inclusive, by 1-4 inclusive, by 1 or 2, by a four-digit Suffix of A, 0, 1 in any combination, may be followed by a two digit alpha-numeric Suffix.
,
, and catalog designation (catalog designation may appear on shipping carton or stuffer sheet).| Last Updated on 2009-04-14 |
Copyright © 2010 Underwriters Laboratories Inc.®
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2010 Underwriters Laboratories Inc.®"